CABLES FOR UNDERGROUND SERVICE AT AERODROMES
5.1 FEATURES OF THE CABLES
5.1.1 Characteristics of cables for underground service
5.1.1.1 Insulation. The following insulation
materials are commonly specified because they provide the
maximum rated conductor temperatures for operating, overload, and short‑circuit conditions for cables
rated up to a maximum of 35 kilovolts:
(a) Cross‑linked polyethylene (XLP). This thermo‑setting
compound has excellent electrical properties, good chemical resistance, good
physical strength characteristics, and remains flexible at low temperatures.
(b) Ethylene‑propylene
rubber (EPR). This
compound has electrical properties which are considered equal to cross‑linked
polyethylene; therefore, the contractor should be given the option to provide
either type.
5.1.1.2 The following insulation materials may be
used where special circumstances warrant their lower rated conductor
temperatures or their lower rated maximum voltage class.
(a) Rubber. Rubber insulated conductors provide ease of
splicing, good moisture resistance, and low dielectric losses.
(b) Varnished cambric. Varnished cambric insulation is used for
resistance to ozone and oil and for ease of splicing. Use varnished cambric
principally in conjunction with paper‑insulated cable
where oil migration is a problem. Where installed in wet or highly humid
locations or underground, varnished‑cambric insulation must be provided
with a suitable sheath.
(c) Paper insulated. Use paper insulated cable for low ionization,
long life, high dielectric strength, low dielectric losses, and good stable
characteristics under temperature variations. As with varnished‑cambric
insulation, paper insulation requires a suitable protective metallic sheath. It may be specified as an option when existing cables
are paper insulated, or as a requirement when the extra cost is justified
because neither cross‑linked polyethylene or ethylene‑propylene
rubber provide the required qualities.
(d) Butyl rubber. This thermosetting
insulation has high dielectric strength and is highly resistant to moisture,
heat, and ozone. It can be used up to 35 kilovolts, but has lower rated
conductor temperatures than either cross‑linked polyethylene or ethylene‑propylene
rubber.
(e) Silicone rubber. This thermosetting insulation is highly
resistant to T7‑eat, ozone, and corona. It can be
used in wet or dry locations, exposed, or in conduit. It has the highest rated
conductor temperatures but can be used only for applications up to five
kilovolts.
5.1.1.3 Cable sheaths
(a) Non-metallic. Non-metallic sheaths should be flexible,
moisture repellent, and long lasting. Neoprene, which is often used as non-metallic
cable sheaths, is unsuitable in many locations. This material frequently
absorbs excessive amounts of water which may penetrate through to the
insulation. Some non-metallic‑sheath materials, especially in some
tropical areas, are reported to be damaged by micro‑organisms, insects.
and plant life. Some sheath materials, which perform well where installed
underground or in conduits, deteriorate rapidly if installed where it is
exposed to sunlight. Materials which become brittle at low temperatures should
not be used in cold regions. In some locations, rodents frequently damage non-metallic‑sheathed
cable. In these areas the cable should be installed in ducts or metallic‑sheathed
cable should be used.
(b) Metallic. Cables exposed to mechanical damage or high
internal pressure require a metallic sheath, such as lead, aluminium, or steel.
Certain insulations, such as paper and varnished cambric, require such
protection in all cases.
5.1.1.4 Cable coverings A suitable covering or jacket may be required for corrosion protection of metallic sheaths.
5.1.1.5 Shielded cables. Shielding of a medium‑voltage distribution
cable is required to confine the electric field to the
insulation itself and to prevent leakage currents
from reaching the outside surface of the cable. Insulation shielding is required on all non-metallic‑shielded cable rated two kilovolts
and above, except for aerodrome‑lighting
series‑circuit cables, and all metallic‑sheathed cable rated five kilovolts and above. Shields should be grounded to reduce the hazards of
shock. Grounding is required at each termination,
otherwise dangers induced shield voltages may
occur. I I
5.1.1.6 Cable fireproofing Cables in
manholes, handholds, and transformer vaults operating at 2 400 volts or over,
or exposed to the failure of other cables operating at these voltages, should
be fireproofed with a suitable spray coating. Exceptions may be made where
physical separation, isolation by barriers, or other considerations permit.
5.1.1.7 Protection against corona damage. Insulation of high‑voltage
cables which may be damaged by ozone should be protected against this damage by
controlling corona, which produces ozone, by placing a thin semi‑conducting
film between the conductor and its insulation. This film fills the voids
between the conductor and the insulation thus preventing the generation of
corona and hence ozone. (See 5.1.3.6.)
5.1.1.8 Cable conductors. Annealed copper is used in most forms of
insulated con doctors because of its high conductivity, flexibility, and ease
of handling. Medium hard‑drawn copper has greater tensile strength than
annealed copper. Aluminium con doctors may be
permitted as a conductor's
option except where corrosive conditions.1imit their usage.
5.1.2 Classes of service
5.1.2.1 Low‑voltage cables. Low‑voltage cables ‑‑
insulation rated at 600 volts or less – are used to connect the second Aries of
series/series isolating transformers to the lamps
in the fixtures, for low‑voltage distribution circuits, and as low‑voltage feeder circuits to single units and the shorter circuits. The conductors
are usually copper but may be aluminium, and either
single‑ or multi‑conductor cables are used. Bothb solid and
stranded conductors are used but stranded is preferred if frequent flexing of the cable is expected. The cross‑sectional area
of the conductor may vary from 2 mm2 to 8 mm2 or larger
if necessary to decrease the voltage drop.
5.1.2.2 High‑voltage cables For aerodrome lighting,
high‑voltage cables are used mostly for source power distribution and
feeder cables. The criteria and materials are the same as for
power distribution cables discussed in
paragraphs 2.5.5 to 2.5.7. The voltages used usually range from 1 000 to 5 000
volts. Conductor sizes usually are in the range of 3.3 mm2 to 21 mm2 in cross‑section
but larger sizes are occasionally used. These cables may be either single‑conductor
or two‑ or three‑conductor cables. Consider the soil, environment,
method of installation, subjection to chemicals, and any special problems in selecting
the insulation,
jackets, sheathing, and
shielding for these cables.
5.1.2.3 Series aerodrome lighting cables. The requirements of the
cables for this purpose have been standardized more
than have the cable requirements for most power circuits.
The series current used in these circuits is between 6 and 20 amperes. The conductor size commonly used is 8.4 mm2 in cross‑section but some
3.3 MM2 cable is also used. These cables are
single‑conductor. The conductor is usually stranded but solid conductor can also be used. The insulation is usually 5 000‑volt
rated. A non‑metallic jacket over the insulation is commonly used.
Metallic‑tape shielding between the insulation and jacket or between the
jacket and non‑metallic covering is often used but may not be required for some installation. The preferred series‑lighting
cables are stranded, copper, 8.3 mm2 conductor; cross‑linked
polyethylene, ethylene‑propylene‑rubber, or Buna‑rubber
insulation; chlorosulfonated polyethylene, polyvinyl chloride, polyethylene, or heavy duty neoprene jacketed; metal‑tape shielded
types.
5.1.2.4 Control cables. Control cables are low‑voltage cables
usually in pairs or multi‑conductor. A group of single‑conductor
cables may be used for some simple control circuits.
Some control cables have one or two larger conductors for the line voltage and/or neutral and several smaller conductors for the individual
controls. Other installations may use a pair of larger wires
for the line and neutral and other cables with many
smaller conductor wires for the individual controls. Multi‑conductor
control cables have 7, 12,
16, or many more conductors are used. Most control cables have stranded copper conductors. The size of the conductor is selected to
keep the line voltage drop within an acceptable range. The
cross‑sectional size of the conductors is usually
between 3.3 mm2 and 0.5 mm2. The insulation resistance rating must be suitable for the control voltage which is usually 250 volts or less. Rubber,
polyethylene, poly vinyl chloride, varnished cambric, and paper
are some of the types of insulation for control
cables. Thin insulation is desirable to reduce the diameter of the cable. Twisted pairs or spiralling of the conductors is desirable for
alternating‑current control circuits to reduce the induced voltage
between circuits. Multi‑conductor cables must have
an outside jacket and may be shielded with metal tape.
5.1.2.5 Communications cable. Special intercommunications or telephone
circuits should be installed to provide communications between control tower,
lighting vaults, and offices or stations. The circuits are usually one or more
twisted‑pair telephone type cable These cables
should be suitable for underground installation. Although the control cables
may be used for communications at some installations, separate cables in
separate conduits or well separated in the trench, if direct burial, are
preferred.
5.1.2.6 Ground wires. A ground wire or counterpoise wire should be
installed to protect underground power and control cables
from high ground current surges in areas where
damage from lightning strikes may be expected. The ground wire should be installed
between the earth's surface and the underground cables. It is usually an
uninstalled, stranded copper conductor. The size of this ground wire should be
not less than the largest size conductors which it protects. Cross‑section
area of the conductor may range from 8.4 mm2 to 21
mm2 or larger. It should be a continuous conductor and connected
to each fixture, light base, and ground rod or connection along its route.
5.1.3 Causes of cable damage
5.1.3.1 Cable faults are frequent reasons for
aerodrome lighting circuit failures and often require
considerable time and effort to locate and repair. Effective methods of reducing cable faults improve reliability of the system. Better
knowledge of the causes of damage to cable should aid in
choosing types of cable and installation procedures.
Some of these causes are discussed below.
5.1.3.2 Mechanical damage Probably most cable faults are
caused by mechanical damage. Poor installation techniques and procedures are
probably the most common cause of mechanical damage, but frost heaves,
vibration from aircraft or vehicle traffic, rodents,
ground shifting or settling, and many other reasons may physically damage the cable. Some types of mechanical damage are:
(a) Nicks and scrapes of the
insulation.
(b) Over stressing of the cable when pulling into
ducts or unrolling the cable for direct burial.
(c) Stones or foreign objects in the beds or
backfills of trenches.
(d) Inadequate slack at entrances to or inside of handholds, manholes, light
bases, conduits, fixtures, connections to equipment, connectors, splices, along
trenches or conduit, or other locations where settling, maintenance,
installations, or weather may increase stresses.
(e) Nicking of the conductor at splices or
connector joints may later break the conductor.
(f) Inadequate separation of cables in trenches, either vertically or horizontally, at slack loops of cable, or places where earth compaction or freezing action may force two sections of cable into direct contact.
(g) Freezing or frost heaves forcing the cable against ice, frozen
earth, or any other solid object or material. Proper cushioning and slack to
reduce stress at these points is necessary.
(h) Improperly
supported cables in manholes or other areas where sagging or exposure may
result in objects or persons putting pressure on the cable.
(f) Vibration from traffic passing over the cable or from equipment
operation attached to or near the cable may cause fatigue of the conductor or
of the jacket and insulation. Where such conditions may exist or be developed,
install the cables in ducts which extend well beyond the area of
vibration.
(j) Breaking or separation of conduits or ducts may break the cable. The
installation of the ducts and conduit must be properly joined and suitably
backfilled and tamped.
5.1.3.3 Water penetration. A ground fault is formed when water is able
to penetrate through the cable sheath and insulation to the conductor. Water
penetration or leakage may occur at splices, connections, cable terminations,
physical damage areas, unsatisfactory insulation, pinholes from lightning or
over voltage, or other defects.
(a) Improperly made splices and improperly installed connector kits are
a frequent source of water penetration. See Section 5.2 for instructions for
making splices and installing connectors.
(b) In order
to avoid water penetration at the ends of cable, these ends should be kept
clean and free from moisture before as well as after connecting to the
equipment. The ends of spare cables should be similarly protected. Some types
of insulation, especially paper and mineral filled, may attract moisture from
the atmosphere during periods of high humidity. The ends of the cables of these
types should be kept sealed at all times even after connecting to the
equipment.
(c) Some insulations, either from defects or composition, may permit
excessive water penetration. Quality tests of insulation resistance should
detect such defects. There are reports that some neoprene‑jacketed cable
is not adequately water resistant, although other reports state that cable of
this type performs well. Before cable is purchased, the performance of the type
of cable at other installations, preferably from the same manufacturer, should
be investigated.
(d) Lightning strikes may severely damage cables
or the induced voltages may be enough to damage the insulation by creating
pinholes. These pinholes are more likely to occur at points of crossing cables
or where the cable is near or in contact with metal conductors. Properly
installed ground wire or counterpoises should reduce the damage from lightning
strikes.
(e)
Excessive voltage may be applied to a cable, either accidentally or from faulty
operation. Damage to the cable may not be noticeable immediately.
5.1.3.4 Chemical damage Often aerodrome lighting
cables are located in areas where fuel, oil, acids, or other chemicals may be
present regularly or occasionally. These chemicals
affect the insulation resistance of some types of cables. If it is known, or suspected, that cables may be exposed to such chemicals, select a type
of cable which is resistant to these chemicals.
5.1.3.5 Rodent damage‑. In some areas,
direct burial cable is damaged by rodents, especially
gophers, gnawing g the insulation. There is some evidence that the rodents may be
attracted to the cable either by the heat emitted from it or by its taste.
Where rodent damage is a serious problem, it may be desirable to install the
cable in ducts or to use metal‑sheathed cable.
5.1.3.6 Micro‑organism or plant damage Micro‑organisms and
plants are reported to have damaged some types of cables in tropical or
subtropical areas. Other types of cable are not seriously
affected. If it is anticipated that such problems may occur, select a type of cable which is known to be resistant to such micro‑organisms
and plants.
5.1.3.7 Ozone and corona damage. Some cable insulations are damaged by ozone and thus
by the corona produced by the circuit or by nearby
circuits. Cable insulations are available which satisfactorily resist these
effects. Select cables with these qualities if the
cable is carrying high voltages or may be exposed to other sources of ozone or corona. In the past some States have used cables which
were not protected against corona damage for runway
and approach light series systems reasoning that these systems are operated at full intensity for only a relatively small number of
hours per year. Consequently, these cables are subjected to
high‑voltage stress during only a small fraction
of the time in service.
This practice has been found to be undesirable
since the reduction in cost is small and because some of this cable invariably
is inserted into the power distribution circuits and are
subjected to continuous high‑voltage stress.
5.1.3.8 ' Ultraviolet damage Some cable insulation, which performs satisfactorily in underground installations, may become brittle and deteriorate rapidly where exposed to sunlight if used on elevated supports such as approach light towers. If the cable will receive this sort of exposure, select cable with insulation which resists ultraviolet or install the cable in metal conduit.
5.1.3.9 Cable deterioration. Most cable insulation
deteriorates slowly. The service life of underground
cables should be 10 to 20 years.
5.2 CABLE
CONNECTIONS
5.2.1 Cable splices
5.2.1.1 All cable splices should be performed by experienced and qualified
cable splices using high standards of workmanship. Splicing methods and
materials should be of types recommended by the manufacturer of the splicing
material for the particular type of cable being spliced. All cable splices
should meet the following requirements.
5.2.1.2 Power cables insulated for
more than 5 000 volts. Splice kits designed for the type of cable being spliced should be used. When such kits are not available,
taped splices made in accordance with paragraph 5.2.2 may be used. Epoxy or
resin splices should not be used.
5.2.1.3 Power cables with 610‑ to 5 000‑volt
insulation.
Pressure epoxy‑resin
splices
envelopes and cast splice kits designed for the cable should be used in strict conformance with the manufacturer's instructions. Taped splices should
be used only if necessary.
5.2.1.4 Power cables insulated for 600 volts or less. Cast splice kits or
pressure epoxy‑resin splice envelopes suitable for all direct earth‑burial cable
may be used. Taped splices using retrenched or heat‑shrinkable
tubing as a covering may also be used.
5.2.1.5 Control and telephone cables. A type of re‑enterable
filled splice envelope is available for use on thermoplastic‑insulated
non‑pressurised cables. Splices to existing
pressurised, lead‑covered, or paper‑insulated cables should be in
accordance with the requirements of the authority
involved.
‑5.2.2 Taped splices
5.2.2.1 Taped splices are usually used only when
satisfactory connectors and splice kits cannot be obtained. If taped splices
are to be made, the correct technique must be used in order to obtain
satisfactory service. The technique described below is intended for single‑conductor
cable but applies with suitable adoption to multi‑conductor cable splice.
5.2.2.2 Keep the ends of the cables to be joined
clean and protected from moisture at all times.
5.2.2.3 Carefully taper and remove the covering, jacket, metallic shield,
sheath, and insulation from the ends of the cables to be joined. Remove all
traces of insulation from the conductors for a length of approximately
5.2.2.4 Use a crimp‑type connector to join the
ends of the conductor. Crimp the connector onto the ends of
the conductors using a tool designed to make a complete crimp before the tool can be removed (see Figure 5~1b). The conductor
connector may also be soldered if desired.
5.2.2.5 Using rubber or synthetic rubber tape of good quality, carefully wrap
the joint one layer at a time maintaining enough tension on the tape for
approximately 25 per cent elongation and overlapping the tape
approximately 50 per cent of its width. Each
layer will extend further up the taper along the insulation. Continue this
build up of layers of rubber tape to the full size
of the insulation layer. See Figure 5‑1c.
5.2.2.6 If shielding tape is used
over the insulation, connect the metal tape, which should
have been kept intact, across the splice by soldering or using suitable connectors. Wrap with extra metal tape of similar type if needed.

5.2.2.7 Continue to wrap the rubber tape as in
5.2.2.5 to not less than 1.5 times the diameter of the cable.
Carefully apply tension on the tape to prevent any voids and obtain good adhesion to the cable surfaces and each inside
layer of tape.
5.2.2.8 Over the rubber, add several layers of high‑insulation‑resistance, flame‑retardant, weather‑ and cold‑resistant tape.
Apply the plastic tape with appreciable tension and overlapping each turn by
approximately 50 per cent of its width. The plastic
tape should extend for
5.2.2.9 If the cable has a steel‑armour or
other metallic cover, connect a length of grounding
braid across the splice and fasten to the armour on the cable with suitable clamp connectors and/or solder on each side of the splices (see Figure 5‑2a).
If the cable is lead encased, make a suitable wiped‑lead
joint over the splice to provide a waterproof seal to the lead
covering on the cable. If the metal covering is protected from corrosion by a coating, apply a coating of similar material over
the entire surface of the cable and splice in the area of this
work.
5.2.3 Connector kits for aerodrome lighting
5.2.3.1 Use of connector kits. In recent years most series‑circuit
connections have been made using connector kits. Although the
cost of connector kits is significant, the time
saved in installation and the ease with which circuits can be opened and resoled when locating faults have made their use desirable. Since the leads of
most isolating transformers are now manufactured with
connectors, cable connectors are required and provide
an easy means of connecting or disconnecting the transformer
into the series circuit and to the
light. Single‑conductor
connectors are shown in Figure 5‑3.
5.2.3.2 Installation of connectors. The cable ends should be
prepared carefully in accordance with the instructions, keeping both the cable
ends and the connector surfaces free of dirt and moisture. Make certain that
any cavities between the cable and interior of the connector are filled with the gel provided to prevent voids. After joining the connectors
ensure that air is not trapped which may tend to force the connection apart.
Taping over the joint with vinyl electric tape to keep the area clean and from separating is suggested.
5.2.4 Coaxial cables
5.2.4.1 Non‑pressurized coaxial cables. Coaxial cable should be
joined using appropriate coaxial connectors. Each connector should be covered
with a
5.2.4.2 Splices in pressurized coaxial cables. No field‑installed
splice in pressurized coaxial
cable should be allowed unless specifically authorised.


5.2.5 Connection of conductors
5.2.5.1 Power conductors. Connections of cable
conductors should be made using crimp connectors utilizing a crimping
tool designed to make a complete crimp before the tool can be removed. Split‑bolt connectors may be used for low‑voltage
circuits of 600
volts or less.
5.2.5.2 Control and telephone cables. Joining of telephone or
control conductors should be done with a twisted and soldered
splice or an appropriate self‑stripping, reinsulated
connector installed with the specific tool designed to crimp the connector. Colour coding of the conductors should be followed throughout the
installation.
5.2.5.3 Cable armour and shields. Armour shields should be
electrically bonded across the splice by cleaning and soldering. Use sections
of metal braid and conducting tape, if needed. Armour and
shielding should be completely insulated from each and from ground, except as
noted in paragraph 4.5.3.3.